_icone_montair_tecnologie_chilled_water_dual_coil.png

montair tech_ec_inverter_plug_fan_2025.png

DOP/SZ 0025÷0092

CHILLED WATER DUAL COIL UNITS WITH EC INVERTER PLUG-FAN

_icona_montair_chilled-water.png _icona_montair_DUAL-COIL.png _icona_montair_EC-Inverter-Plug-fan.png _icona_montair_EC-Inverter-Plug-fan_HESP.png _icona_montair_60-Hz.png

Dual Coil units with two independent cooling circuits, both with chilled water. The circuits are connected with two water cooled or air cooled liquid Chillers, with Free-Cooling technology too. The two circuits are separated with nonsimultaneous start-up, for back-up operation.
The DOP range is equipped with EC Inverter Plug-Fans; High Head fans are available as accessories.
The EC Inverter Plug-Fans allow fuel consumption at partial loads to be reduced by up to 61% compared to centrifugal fans, modulating the power consumption according to the required thermal load.
The DOP range is available in two air discharge versions: DOPT with top air discharge and DOPB with bottom air discharge.
Unit supervision is developed by means of Modbus RTU protocol over RS485
serial interface as standard configuration. Other communication protocols and
interfaces are available as option.

Versions

  • DOPT/SZ - Top air discharge and frontal intake
  • DOPB/SZ - Bottom air discharge and upper intake

Power range

  • 25.0-91.0 kW
  • 7.1-26.0 Ton

Factory fitted accessories

  • AP High ESP fans
  • HT High water temperature operation 13/18°C
  • CM Scheduler
  • DPS Double power supply
  • EC EC Inverter fans
  • AR Air renewal inlet with filter
  • AT Constant air flow regulation control
  • AT/P Constant available static pressure regulation control
  • PA Differential pressure switch fans control
  • PF Differential pressure switch filters control
  • ES Electrical heater with step regulation
  • WS2 Hot water coil with 3-Way valve
  • UMI Electrodes steam humidifier
  • WM Web Monitoring - Wireless remote monitoring (GPRS/EDGE/4G/TCP-IP)
  • SA Water alarm sensor
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISB1 BACnet MSTP protocol, RS485 serial interface, BTL certified.
  • ISBT1 BACnet IP protocol, Ethernet port, BTL certified.
  • ISS SNMP protocol, Ethernet port
  • RE Adjustable minimum/maximum voltage and phase control relay

Loose accessories

  • MP Condensate drain pump
  • MP/U Condensate and humidifier drain pump
  • SB Fire sensor
  • SC Smoke sensor
  • CR Remote control panel
  • ZP Adjustable baseframe with shock absorbers (mod. B only)
  • ZA Adjustable baseframe with shock absorbers and deflector (mod. B only)
  • DL Bottom plenum for side connections (mod. T only)
  • BA Top vertical intake plenum with F7 efficiency filter (mod. B only)
  • BD Top frontal discharge plenum with grid (mod. T only)
  • DM Bottom frontal discharge plenum with grid (mod. B only)
  • BV Top discharge/intake plenum with damper
  • BF Direct Free-Cooling plenum for units with bottom air discharge
  • DF Direct Free-Cooling plenum for units with top air discharge
00250033005000700092
PRIMARY COOLING circuit performancesTotal cooling capacity (1)kW24,833,150,169,991,4
Sensible cooling capacity (1)kW24,432,248,867,287,1
SHR (1)%98%97%97%96%95%
Water flow (1)l/s1,181,582,393,334,36
Total pressure drops (1)kPa2422313236
SECONDARY COOLING circuit performancesTotal cooling capacity (1)kW24,833,150,169,991,4
Sensible cooling capacity (1)kW24,432,248,867,287,1
SHR (1)%98%97%97%96%95%
Water flow (1)l/s1,181,582,393,334,36
Total pressure drops (1)kPa2422313236
Fan sectionFans11223
Air flow (2)m³/h97009700138001880022800
Max. available static pressure - STD fansPA410375350395400
Max. available static pressure - High ESP fansPA535495505500515
FiltersTipoG4G4G4G4G4
Electrical characteristicsPower supplyV/Ph/Hz380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60
Sound pressureDOPT - Top Air Discharge version (3)dB(A)6061586461
DOPB - Bottom Air Discharge version (3)dB(A)5556535956
ACCESSORIES & ADDITIONAL SECTIONSACCESSORIES & ADDITIONAL SECTIONS
Electrical heatingSteps33333
Electrical powerkW13,513,516,522,527,0
Hot water coilHeating capacity (4)kW18,320,128,439,450,5
Water flow (4)l/s0,890,971,371,902,44
Total pressure drops (4)kPa4040444848
Electrodes steam humidifierNominal steam productionkg/h8881515
Nominal powerkW6,06,06,011,311,3

Dimensions

00250033005000700092
DimensionsLmm13501350175022252625
Wmm890890890890890
Hmm19801980198019801980
WeightsTransport weight DOPT - Top Air Dischargekg473499562752891
Transport weight DOPB - Bottom Air Dischargekg491517592782927
Operating weight DOPT - Top Air Dischargekg453477540719858
Operating weight DOPB - Bottom Air Dischargekg471495570749894

Notes

  • 1 Ambient air temperature 24°C - R.H. 50%, water temperature 7°C / 12°C.
  • 2 Air flow calculated with Available Static Pressure of 20 Pa (0,08 in WG).
  • 3 Sound pressure level calculated in free field conditions at 1,5 m height and 2 m distance. According to ISO 3744.
  • 4 Ambient air temperature 24°C, water temperature 45°C/40°C (post-heating operation).