XOP/SZ 1012÷2148

AIR COOLED DIRECT EXPANSION UNITS WITH SCROLL COMPRESSORS AND EC INVERTER PLUG-FANS

_icona_montair_DX.png _icona_montair_scroll.png _icona_montair_EC-Inverter-Plug-fan.png _icona_montair_EC-Inverter-Plug-fan_HESP.png _icona_montair_XT.png _icona_clint_refrigerant_R410A_2024.png _icona_montair_60-Hz.png

Air cooled direct expansion units. The XOP range features EC Inverter Plug-Fans; high ESP fans are also available as accessory.
The EC Inverter Plug-Fans allow fuel consumption at partial loads to be reduced by up to 61% compared to centrifugal fans, modulating the power consumption according to the required thermal load.
The XOP range is available in two air delivery configurations: XOPT with upflow and XOPB with downflow.
Unit supervision is developed by means of Modbus RTU protocol over RS485
serial interface as standard configuration. Other communication protocols and
interfaces are available as option.
The units are suitable for operation at a high outdoor air temperature (up to 52 C) with the correct combination with the XT remote condensers.

Versions

  • XOPT/SZ - Top air discharge and frontal intake
  • XOPB/SZ - Bottom air discharge and upper intake

Power range

  • 12.0-151 kW
  • 3.5-43.0 Ton

Factory fitted accessories

  • AP High ESP fans
  • SL Unit silencement
  • CM Scheduler
  • EC EC Inverter fans
  • TE Electronic expansion valve
  • AR Air renewal inlet with filter
  • AT Constant air flow regulation control
  • AT/P Constant available static pressure regulation control
  • PA Differential pressure switch fans control
  • PF Differential pressure switch filters control
  • ES Electrical heater with step regulation
  • WS2 Hot water coil with 3-Way valve
  • PG Hot gas post-heating coil (with valve)
  • UMI Electrodes steam humidifier
  • WM Web Monitoring - Wireless remote monitoring (GPRS/EDGE/4G/TCP-IP)
  • SA Water alarm sensor
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISB1 BACnet MSTP protocol, RS485 serial interface, BTL certified.
  • ISBT1 BACnet IP protocol, Ethernet port, BTL certified.
  • ISS SNMP protocol, Ethernet port
  • RE Adjustable minimum/maximum voltage and phase control relay

Loose accessories

  • MP Condensate drain pump
  • MP/U Condensate and humidifier drain pump
  • SB Fire sensor
  • SC Smoke sensor
  • CR Remote control panel
  • ZP Adjustable baseframe with shock absorbers (mod. B only)
  • ZA Adjustable baseframe with shock absorbers and deflector (mod. B only)
  • DL Bottom plenum for side connections (mod. T only)
  • BA Top vertical intake plenum with F7 efficiency filter (mod. B only)
  • BD Top frontal discharge plenum with grid (mod. T only)
  • DM Bottom frontal discharge plenum with grid (mod. B only)
  • BV Top discharge/intake plenum with damper
  • BF Direct Free-Cooling plenum for units with bottom air discharge
  • DF Direct Free-Cooling plenum for units with top air discharge
101210141018102310292036104220472056206410752081209121014112412341352148
PerformancesTotal cooling capacity (1)kW12,215,017,723,229,036,742,648,457,465,776,182,493,3104114127138151
Sensible cooling capacity (1)kW10,112,314,218,723,332,339,239,847,954,164,868,677,887,7102109113119
SHR (1)%83%82%80%80%80%88%92%82%84%82%85%83%83%84%89%86%82%79%
Total absorbed power (1)kW3,44,15,26,27,911,212,114,115,918,022,222,326,329,631,733,339,542,7
EER (1)3,603,643,433,303,663,283,523,433,613,653,433,703,553,513,603,813,493,54
Refrigerant circuitRefrigerant circuits111112122212222222
Compressors111112122212224442
Fan sectionFans111111111222223333
Air flow (2)m³/h3000330039005600560011500115001150011500160001600016000210002100025500255002550025500
Max. available static pressure - STD fansPA450450410285270255240245235300300300350335350350350350
Max. available static pressure - High ESP fansPA835750750730725490475475465565550550520505545525525530
FiltersTipoG4G4G4G4G4G4G4G4G4G4G4G4G4G4G4G4G4G4
Electrical characteristicsPower supplyV/Ph/Hz380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60380/3+N/60
Sound pressureXOPT - Top Air Discharge version (3)dB(A)565861626265656566646863676866676771
XOPB - Bottom Air Discharge version (3)dB(A)515356575760606060586258626361616165
ACCESSORIES & ADDITIONAL SECTIONSACCESSORIES & ADDITIONAL SECTIONS
Electrical heatingSteps333333333333333333
Electrical powerkW4,54,54,57,57,513,513,513,513,516,516,516,522,522,527,027,027,027,0
Hot water coilHeating capacity (4)kW6,87,37,79,210,020,021,521,623,229,231,532,341,543,553,655,155,957,2
Water flow (4)l/s0,330,350,370,440,480,971,051,051,121,411,521,562,002,102,592,662,702,76
Total pressure drops (4)kPa303438273033373742445153434743454648
Hot gas coilHeating capacity (5)kW3,34,04,86,67,910,111,113,615,617,521,122,225,428,430,733,237,842,4
Electrodes steam humidifierNominal steam productionkg/h444448888888151515151515
Nominal powerkW3,03,03,03,03,06,06,06,06,06,06,06,011,311,311,311,311,311,3

Dimensions

101210141018102310292036104220472056206410752081209121014112412341352148
DimensionsLmm6756756758758751350135013501350175017501750222522252625262526252625
Wmm675675675675675890890890890890890890890890890890890890
Hmm198019801980198019801980198019801980198019801980198019801980198019801980
WeightsTransport weight XOPT - Top Air Dischargekg246249253288305484480499534621641679771798982100810061031
Transport weight XOPB - Bottom Air Dischargekg2632672703063225024985175516506707088008271017104410421067
Operating weight XOPT - Top Air Dischargekg236239243277294464460479514599619657743770949975973998
Operating weight XOPB - Bottom Air Dischargekg253257260295311482478497531628648686772799984101110091034

Notes

  • 1 Ambient air temperature 24°C - R.H. 50%, condensing temperature 45°C.
  • 2 Air flow calculated with Available Static Pressure of 20 Pa (0,08 in WG).
  • 3 Sound pressure level calculated in free field conditions at 1,5 m height and 2 m distance. According to ISO 3744.
  • 4 Ambient air temperature 24°C, water temperature 45°C/40°C (post-heating operation).
  • 5 Temperatura aria ambiente 24°C.