XIPR-E 1010÷1035
DIRECT EXPANSION IN RACK ENCLOSURE CONDITIONING UNITS
Enclosure solution allows a complete integration of Rack and Cooling system in a common cabinet. The hot air rejected by the servers is addressed to the cooling unit and cold air flows to the servers without risk of mixing. This solution ensures an efficient and accurate control of the air temperature to the IT apparatus independently on the room conditions. The Rack can be 600 or 800 mm wide and it is matched with a single Direct Expansion cooling module XIPR.
The units are equipped with EC Inverter Plug-Fan fans with backcurved blades and electronic expansion valve directly controlled by a microprocessor and an advanced user interface. The system is completed by an external condenser unit equipped with a high efficiency Scroll Inverter compressor. Both the fans and the compressor work on the basis of dedicated control logics which aim to maximise efficiency in a wide range of operating conditions.
Versions
- XIPR-E - Enclosure type 1200 mm
Power range
- 6.5-43.0 kW
Accessories
Factory fitted accessories
- R6 Rack for Enclosure 600 x 1200 x 42U
- R8 Rack for Enclosure 800 x 1200 x 42U
- MP Condensate drain pump
- SA Water alarm sensor
- IS Modbus RTU protocol, RS485 serial interface
- IST Modbus TCP/IP protocol, Ethernet port
- ISB BACnet MSTP protocol, RS485 serial interface
- ISBT BACnet IP protocol, Ethernet port
- ISS SNMP protocol, Ethernet port
- STT Remote air temperature sensors
- TCF Refrigerant connections from the top
Loose accessories
- CR Remote control panel
Technical data
| 1010 | 1015 | 1025 | 1035 | |||
| Performances | Total Cooling Capacity - Max (1) | kW | 14,1 | 18,4 | 27,6 | 42,5 |
| Total Cooling Capacity - Min (1) | kW | 6,5 | 7,6 | 11,9 | 18,2 | |
| Sensible cooling capacity - Max. (1) | kW | 14,1 | 18,4 | 27,6 | 42,5 | |
| Sensitive cooling capacity - min (1) | kW | 6,5 | 7,6 | 11,9 | 18,2 | |
| SHR - Max (1) | % | 100 | 100 | 100 | 100 | |
| SHR - min (1) | % | 100 | 100 | 100 | 100 | |
| Fans | N° | EC Plug-Fans | EC Plug-Fans | EC Plug-Fans | EC Plug-Fans | |
| Air Flow Rate - Max | m³/h | 2500 | 3000 | 4000 | 5800 | |
| Air flow - min | m³/h | 1250 | 1500 | 2000 | 2900 | |
| Fan energy consumption - Max | kW | 0,18 | 0,28 | 0,40 | 0,67 | |
| Fan energy consumption - min | kW | 0,03 | 0,05 | 0,07 | 0,12 | |
| Power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | |
| COMBINATION WITH CONDENSING UNIT | 1x1010 | 1x1015 | 1x1025 | 1x1035 | ||
| MREI Motor-condensing unit | Compressor | N° | 1 | 1 | 1 | 1 |
| Compressor absorbed power - Max | kW | 3,56 | 4,95 | 8,68 | 8,90 | |
| Compressor absorbed power - min | kW | 1,06 | 1,15 | 1,78 | 2,29 | |
| Condensation fans | N° | 1 | 2 | 2 | 2 | |
| EER - Max | 3,76 | 3,52 | 3,04 | 4,44 | ||
| EER - min | 3,39 | 3,31 | 3,18 | 3,57 | ||
| Power supply | V/Ph/Hz | 230/1/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | |
Dimensions
| 1010 | 1015 | 1025 | 1035 | |||
| Indoor unit dimensions | L (2) | mm | 300+Rack | 300+Rack | 300+Rack | 300+Rack |
| W (3) | mm | 1200 | 1200 | 1200 | 1200 | |
| H | mm | 2073 (42 U) | 2073 (42 U) | 2073 (42 U) | 2073 (42 U) | |
| Weight indoor unit | Weight | kg | 198 | 198 | 207 | 217 |
| Weight - Rack 600 | kg | 175 | 175 | 175 | 175 | |
| Weight - Rack 800 | kg | 205 | 205 | 205 | 205 | |
| Outdoor unit dimensions - MREI | L | mm | 320 | 500 | 500 | 1000 |
| H | mm | 1100 | 1270 | 1270 | 1300 | |
| Outdoor unit weight - MREI | Weight | kg | 123 | 195 | 201 | 275 |
Notes
- 1 Return air 46°C - 20% rh and 35°C outdoor temperature.
Documents
- Product overview (IT) montair_close_control_over_05_2025_ITA_w.pdf
- Product overview (EN) montair_close_control_over_05_2025_ENG_w.pdf
- Product guides (IT) montair_close_control_product_guide_05_2025_ITA_w.pdf
- Product guides (EN) montair_close_control_product_guide_05_2025_ENG_w.pdf
- Commercial leaflets montair_IN-ROW_05_2025_w.pdf
- Technical brochures 06_IN_ROW__IN_RACK_mtb_229_JZFJNl0.pdf