XIPR-ER 1010÷1035
DIRECT EXPANSION IN RACK ENCLOSURE + REDUNDANCY CONDITIONING UNITS
It is also possible to achieve a fully redundant system XIPR-ER by coupling the rack with two direct expansion cooling modules. These systems are flexible, easy to be implemented and they are the perfect solution for different applications such as micro data centers, high density servers, EDGE computing, IOT applications, 5G devices. The two modules can operate in a Master/Slave configuration with one unit working and one unit in stand-by with rotation of the stand-by unit on time basis.
The units are equipped with EC Inverter Plug-Fan fans with backcurved blades and electronic expansion valve directly controlled by a microprocessor and an advanced user interface. The system is completed by an external condenser unit equipped with a high efficiency Scroll Inverter compressor. Both the fans and the compressor work on the basis of dedicated control logics which aim to maximise efficiency in a wide range of operating conditions.
Versions
- XIPR-ER - Enclosure type with Redundancy - 1200 mm
Power range
- 6.5-43.0 kW
Accessories
Factory fitted accessories
- R6 Rack for Enclosure 600 x 1200 x 42U
- R8 Rack for Enclosure 800 x 1200 x 42U
- MP Condensate drain pump
- SA Water alarm sensor
- IS Modbus RTU protocol, RS485 serial interface
- IST Modbus TCP/IP protocol, Ethernet port
- ISB BACnet MSTP protocol, RS485 serial interface
- ISBT BACnet IP protocol, Ethernet port
- ISS SNMP protocol, Ethernet port
- STT Remote air temperature sensors
- TCF Refrigerant connections from the top
Loose accessories
- CR Remote control panel
Technical data
| 1010 | 1015 | 1025 | 1035 | |||
| Performances | Total Cooling Capacity - Max (1) | kW | 14,1 | 18,4 | 27,6 | 42,5 |
| Total Cooling Capacity - Min (1) | kW | 6,5 | 7,6 | 11,9 | 18,2 | |
| Sensible cooling capacity - Max. (1) | kW | 14,1 | 18,4 | 27,6 | 42,5 | |
| Sensitive cooling capacity - min (1) | kW | 6,5 | 7,6 | 11,9 | 18,2 | |
| SHR - Max (1) | % | 100 | 100 | 100 | 100 | |
| SHR - min (1) | % | 100 | 100 | 100 | 100 | |
| Fans | N° | 3 | 3 | 4 | 6 | |
| Air Flow Rate - Max | m³/h | 2500 | 3000 | 4000 | 5800 | |
| Air flow - min | m³/h | 1250 | 1500 | 2000 | 2900 | |
| Fan energy consumption - Max | kW | 0,18 | 0,28 | 0,40 | 0,67 | |
| Fan energy consumption - min | kW | 0,03 | 0,05 | 0,07 | 0,12 | |
| Power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | |
| COMBINATION WITH CONDENSING UNIT | 2x1010 | 2x1015 | 2x1025 | 2x1035 | ||
| MREI Motor-condensing unit | Compressor | N° | 1 | 1 | 1 | 1 |
| Compressor absorbed power - Max | kW | 3,56 | 4,95 | 8,68 | 8,90 | |
| Compressor absorbed power - min | kW | 1,06 | 1,15 | 1,78 | 2,29 | |
| Condensation fans | N° | 1 | 2 | 2 | 2 | |
| EER - Max | 3,76 | 3,52 | 3,04 | 4,44 | ||
| EER - min | 3,39 | 3,31 | 3,18 | 3,57 | ||
| Power supply | V/Ph/Hz | 230/1/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | |
Dimensions
| 1010 | 1015 | 1025 | 1035 | |||
| Indoor unit dimensions | L (2) | mm | 300+300+Rack | 300+300+Rack | 300+300+Rack | 300+300+Rack |
| W (3) | mm | 1200 | 1200 | 1200 | 1200 | |
| H | mm | 2073 (42 U) | 2073 (42 U) | 2073 (42 U) | 2073 (42 U) | |
| Weight indoor unit | Weight | kg | 198 | 198 | 207 | 217 |
| Weight - Rack 600 | kg | 175 | 175 | 175 | 175 | |
| Weight - Rack 800 | kg | 205 | 205 | 205 | 205 | |
| Outdoor unit dimensions - MREI | L | mm | 320 | 500 | 500 | 1000 |
| W | mm | 870 | 1160 | 1160 | 1850 | |
| H | mm | 1100 | 1270 | 1270 | 1300 | |
| Outdoor unit weight - MREI | Weight | kg | 123 | 195 | 201 | 275 |
Notes
- 1 Return air 46°C - 20% rh and 35°C outdoor temperature.
Documents
- Product overview (IT) montair_close_control_over_05_2025_ITA_w.pdf
- Product overview (EN) montair_close_control_over_05_2025_ENG_w.pdf
- Product guides (IT) montair_close_control_product_guide_05_2025_ITA_w.pdf
- Product guides (EN) montair_close_control_product_guide_05_2025_ENG_w.pdf
- Commercial leaflets montair_IN-ROW_05_2025_w.pdf
- Technical brochures 06_IN_ROW__IN_RACK_mtb_229_JZFJNl0.pdf