_icone_montair_tecnologie_chilled_water.png

_montair_tech_ec_inverter_plug_fan.png

WOPR-E 0015÷0030

HIGH PERFORMING CHILLED WATER AIR CONDITIONING UNITS IN RACK ENCLOSURE

_montair_CHILLED_H2O_2015.png _montair_EC_plug_fan_inverter_2015.png _montair_EC_plug_fan_inverter_HIGH_ESP2015.png _montair_HT_2015.png

Enclosure solution allows a complete integration of Rack and Cooling system in a common cabinet. The hot air rejected by the servers is addressed to the cooling unit and cold air flows to the servers without risk of mixing. This solution ensures an efficient and accurate control of the air temperature to the IT apparatus independently on the room conditions. The Rack can be 600 or 800 mm wide and is matched with a single Chilled Water cooling module WOPR.

Versions

  • WOPR-E/C - Enclosure type 1200 mm
  • R6 - Rack for Enclosure 600 x 1200 x 42U
  • R8 - Rack for Enclosure 800 x 1200 x 42U

Power range

  • 19.0-39.0 kW
  • 5.5-11.0 Ton

Factory fitted accessories

  • MP Condensate drain pump
  • DPS Double power supply
  • SA Water alarm sensor
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISS SNMP protocol, Ethernet port
  • MVP 2 way modulating and balancing valve with flow meter, pressure independent
  • MQ 3-Way modulating valve
  • OW Outlet water temperature sensor
  • TCI Hydraulic connections from the top

Loose accessories

  • CR Remote control panel
0015002000250030
PerformancesTotal cooling capacity (1)kW19,225,831,839,3
Sensible cooling capacity (1)kW19,225,831,839,3
SHR (1)%1111
FansTipo3346
FansEC Plug-FansEC Plug-FansEC Plug-FansEC Plug-Fans
Air flowm³/h3000400054005800
Fan energy consumptionkW0,310,430,520,67
Water flow (1)l/s0,751,031,271,56
Pressure drops (1)kPa49,039,346,061,1
Power supplyV/Ph/Hz230/1/50230/1/50230/1/50230/1/50
Weight indoor unitWeightkg200206211216
Weight - Rack 600kg175175175175
Weight - Rack 800kg205205205205

Dimensions

0015002000250030
Indoor unit dimensionsL (2)mm300+Rack300+Rack300+Rack300+Rack
W (3)mm1200120012001200
Hmm2073 (42 U)2073 (42 U)2073 (42 U)2073 (42 U)

Notes

  • 1 Return air 46°C - 20% rh and 14/20°C water temperature.
  • 2 Rack 600 mm or Rack 800 mm width.
  • 3 Nominal dimension (overall dimension 1250mm).