LRE/FC

LRE/FC - LOGICA AIR COOLED LIQUID CHILLERS FREE-COOLING WITH SCROLL COMPRESSORS AND EC INVERTER FANS

_icona_montair_assiale_ec_inverter.png _icona_montair_scroll.png _icona_montair_plate.png _icona_montair_FC.png _icona_clint_refrigerant_R410A_2024.png

LRE/FC - LOGICA AIR COOLED LIQUID CHILLERS FREE-COOLING WITH SCROLL COMPRESSORS AND EC INVERTER FANS

Versions

  • LRE/FC - Cooling only

Features

  • 5 sizes with cooling capacity from 58 to 188 kW (from 17 to 54 TON)
  • EC Inverter axial fans
  • Scroll compressors
  • Plate exchanger
  • Double circulating pump
  • Free-Cooling
  • 5 sizes with cooling capacity from 279 to 821 kW (from 79 to 233 TON)
206020802100315042006250630084001050012750
PerformancesCooling capacity (1)kW58,271,699,5148188279330428530821
Absorbed power (1)kW18,224,030,946,765,878,888,5118152252
EER (1)3,273,423,083,063,273,543,733,613,503,25
Power supplyV/Ph/Hz400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50
Free Cooling 100%Air temperature (2)°C8,16,34,96,65,37,77,36,96,56,9
Absorbed power (2)kW224681616202436
CompressorsQuantity2223468101012
Circuits1111222222
Capacity steps2223468888
Water circuitWater flowl/s3,033,735,187,699,7914,5017,2022,3027,6042,70
Sound pressureSTD version (3)dB(A)59595960616769707175
With SL accessory (3)dB(A)57575758596466676771

Dimensions

206020802100315042006250630084001050012750

Notes

  • 1 Chilled water (with ethylene glycol at 30%) from 20 to 15°C, ambient air temperature 35°C.
  • 2 Ambient air temperature at wich the cooling capacity indicated in point (1) is reached.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) The nominal inlet/outlet water temperature at note (1) is 3 degrees lower than nominal inlet/outlet water temperature on cooling door to take into account the presence of LPS Leak Prevention System.