LRE/Y/FC

LRE/Y/FC - LOGICA AIRCOOLED LIQUID CHILLERS FREE-COOLING WITH SCREW COMPRESSORS AND EC INVERTER FANS

_montair_icon_EC_Axial_fans_2015.png _montair_Screw_2015.png _montair_icon_shell_2015.png _montair_FC_2015.png _montair_icon_refrigerant_R134a_14.png icon_refrigerant_R513A.png

LRE/Y/FC - LOGICA AIRCOOLED LIQUID CHILLERS FREE-COOLING WITH SCREW COMPRESSORS AND EC INVERTER FANS

Versions

  • LRE/Y/FC - Cooling only

Features

  • 5 sizes with cooling capacity from 291 to 808 kW (from 83 to 230 TON)
  • EC Inverter axial fans
  • Screw compressors
  • Shell and tube exchanger
  • Double circulating pump
  • FREE-COOLING
  • On request, units can be supplied with R513A refrigerant
23002350250025502800
PerformancesCooling capacity (1)kW291364474567808
Absorbed power (1)kW82,698,4122147214
EER (1)3,463,703,883,863,77
Power supplyV/Ph/Hz400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50
Free Cooling 100%Air temperature (2)°C7,77,06,96,66,6
Absorbed power (2)kW12,814,014,019,225,6
CompressorsQuantity22222
Circuits22222
Capacity stepsSteplessSteplessSteplessSteplessStepless
Water circuit.Water flowl/s13,917,422,627,138,6
Sound pressureSTD version (3)dB(A)7778787980
With SL accessory (3)dB(A)7576767778

Dimensions

Notes

  • 1 Chilled water (with ethylene glycol at 30%) from 20 to 15°C, ambient air temperature 35°C.
  • 2 Ambient air temperature at wich the cooling capacity indicated in point (1) is reached.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) The nominal inlet/outlet water temperature at note (1) is 3 degrees lower than nominal inlet/outlet water temperature on cooling door to take into account the presence of LPS Leak Prevention System.