LRE

LRE - LOGICA AIRCOOLED LIQUID CHILLERS WITH SCROLL COMPRESSORS AND EC INVERTER FANS

_montair_icon_EC_Axial_fans_2015.png _montair_Scroll_inverter_2015.png _montair_Scroll_2015.png _montair_icon_plate_2015.png _montair_icon_refrigerant_R410A_14.png

LRE - LOGICA AIRCOOLED LIQUID CHILLERS WITH SCROLL COMPRESSORS AND EC INVERTER FANS

Versions

  • LRE - Cooling only
  • LRE/SSL - Super silenced cooling only

Features

  • 5 sizes with cooling capacity from 59 to 195 kW (from 17 to 56 TON)
  • EC Inverter axial fans
  • Scroll compressors (Inverter Scroll also available on request)
  • Plate exchanger
  • Double circulating pump
  • 5 sizes with cooling capacity from 248 to 763 kW (from 71 to 217 TON)
206020802100315042006250630084001050012750
PerformancesCooling capacity (1)kW58,674,392,0142195248299394491763
Absorbed power (1)kW17,921,729,946,459,782,792,5118154254
EER (1)3,273,423,083,063,273,003,233,333,193,01
Power supplyV/Ph/Hz400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50
CompressorsQuantity222346681012
Circuits1111222222
Capacity steps222346681010
Water circuit.Water flowl/s2,803,554,406,809,3111,9014,3018,8023,5036,50
Sound pressureSTD version (2)dB(A)56606061616669706973
With SL accessory (2)dB(A)54585859596366666670
SSL version (2)dB(A)52565655-5961606165

Dimensions

Notes

  • 1 Chilled water from 20 to 15°C, ambient air temperature 35°C.
  • 2 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) The nominal inlet/outlet water temperature at note (1) is 3 degrees lower than nominal inlet/outlet water temperature on cooling door to take into account the presence of LPS Leak Prevention System.