LREXT/Y
LREXT/Y - LOGICA AIRCOOLED LIQUID CHILLERS WITH SCREW COMPRESSORS AND EC INVERTER FANS FOR HIGH EXTERNAL AMBIENT TEMPERATURE (UP TO 52°C)






LREXT/Y - LOGICA AIRCOOLED LIQUID CHILLERS WITH SCREW COMPRESSORS AND EC INVERTER FANS FOR HIGH EXTERNAL AMBIENT TEMPERATURE (UP TO 52°C)
Versions
- LREXT/Y - Cooling only
Features
- 5 sizes with cooling capacity from 276 to 840 kW (from 79 to 239 TON)
- EC Inverter axial fans
- Screw compressors (Inverter Screw also available on request)
- Shell and tube exchanger
- Double circulating pump
Technical data
2250 | 2300 | 2400 | 2500 | 2750 | |||
Performances | Cooling capacity (1) | kW | 276 | 350 | 492 | 610 | 840 |
Absorbed power (1) | kW | 69,9 | 88,1 | 124 | 153 | 212 | |
EER (2) | 3,95 | 3,97 | 3,96 | 3,99 | 3,96 | ||
Power supply | V/Ph/Hz | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | |
Compressors | Quantity | n° | 2 | 2 | 2 | 2 | 2 |
Circuits | n° | 2 | 2 | 2 | 2 | 2 | |
Capacity steps | n° | Stepless | Stepless | Stepless | Stepless | Stepless | |
Water circuit. | Water flow | l/s | 11,4 | 13,6 | 17,7 | 22,6 | 35,6 |
Sound pressure | STD version (3) | dB(A) | 68 | 68 | 70 | 71 | 72 |
Dimensions
Notes
- 1 Chilled water from 20 to 15°C, ambient air temperature 35°C.
- 2 Chilled water from 20 to 15°C, ambient air temperature 46°C.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- N.B. (1) The nominal inlet/outlet water temperature at notes (1) and (2) is 3 degrees lower than nominal inlet/outlet water temperature on cooling door to take into account the presence of LPS Leak Prevention System.
Documents
- Product overview (IT) _montair_close_control_over_2023_ITA_w.pdf
- Product overview (EN) _montair_close_control_over_2023_ENG_w_mLQrzHm.pdf
- Product overview (ES) _montair_close_control_over_2023_SPA_w.pdf
- Product guides (IT) _montair_close_control_product_guide_2023_ITA_w_TdrD7Bl.pdf
- Product guides (EN) _montair_close_control_product_guide_2023_ENG_w_mV3CzWD.pdf