UCM/SZ/EC/SL 1512T÷2854

UCM/SZ/EC/SL 1512T÷2854

SILENCED REMOTE AIR COOLED CONDENSER WITH EC INVERTER FANS

_icona_montair_assiale_ec_inverter.png _icona_montair_SL.png _icona_clint_refrigerant_R410A_2024.png _icona_montair_60-Hz.png

Air remote condensers with axial fans coupled to the units of the XIP/SZ – TIP/SZ – XOP/SZ – TOP/SZ series.
The units are available in two different configurations depending on the noise level required: Standard and Silenced (SL). The units are equipped with the latest generation axial fans, with motor fan shrouds having a large radius of curvature to eliminate all the air flow turbulence and with larger plenum to uniform the air distribution on the cooling coil.
The Remote Condensers are provided with all necessary wiring and electrical protection already on board. The Condensing Control / Fan Speed Control is included for a continuous modulation of the fans speed. EC Inverter fans are available for a full modulation of absorbed power and noise according to the required air flow.
The units can be installed with either horizontal or vertical air delivery, with dedicated supports (SVV), available as accessory.

Versions

  • UCM/SZ/EC/SL - Silenced remote condenser

Factory fitted accessories

  • EC EC Inverter fans
  • SVV Supports for vertical air flow versions
1512T1513T1522T1523T1622T1623T1624163216331634164316442622262326242632263326342643264428342843284428532854
UCM/SZ/EC/SLAir flowm³/h4500400090008000182001680015500273002520023250336003100018200170001570027300255002300034000306503500050000440006250055000
Liquid lineØ1216181818222222222222222x162x182x182x182x182x182x182x222x222x222x222x222x22
Gas lineØ1618282828353535353535352x222x282x282x282x282x282x282x352x352x352x352x352x35
Refrigerant circuits1111111111112222222222222
Power supplyV/Ph/Hz380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60380/3/60
Absorbed power unit with EC Inverter fanskW0,160,160,330,330,870,961,011,471,441,521,922,020,870,991,051,311,481,481,981,961,932,402,213,002,77
Fans1122222333442223334434455
Sound pressure unit with EC Inverter fansdB(A)36363939424344454546464742434544454646474544454546

Dimensions

1512T1513T1522T1523T1622T1623T1624163216331634164316442622262326242632263326342643264428342843284428532854
DimensionsLmm1200120019001900230023002300320032003200410041002300230023003200320032004100410039005000500061006100
Wmm96096096096096096096096096096096096096096096096096096096096012901290129012901290
Hmm800800800800105010501050105010501050105010501050105010501050105010501050105013801380138013801380
WeightsTransport weight unit with EC Inverter fanskg9194140146226237249325339356441463226237249322339356441463460567602707750
Operating weight unit with EC Inverter fanskg7376111118184195206266280297365388184195206263280297365388390478512597641

Notes

  • N.B. (1) Combinations with Close Controls models are specified on the dedicated Close Control pages.