_icone_montair_tecnologie_underfloor_CW.png

_montair_tech_ec_inverter_plug_fan.png

WOPU 0120÷0280

CHILLED WATER UNDERFLOOR UNITS WITH EC INVERTER PLUG-FANS

_montair_CHILLED_H2O_2015.png _montair_UNDER_2018.png _montair_EC_plug_fan_inverter_2015.png _montair_EC_plug_fan_inverter_HIGH_ESP2015.png _montair_HT_2015.png

New generation Chilled Water units characterized by the combination of two parts: the upper cooling module which includes an high performing coil, filters, electrical box, modulating valve and the newest EC Inverter Plug-Fans are housed in a dedicated module optimized for minimum air pressure drops and reduced electrical absorbed power. The fan module, normally configured "fully open" for installation under the raised floor, can be provided with panels for installation above the raised floor.
Unit supervision is developed by means of Modbus RTU protocol over RS485
serial interface as standard configuration. Other communication protocols and
interfaces are available as option.
These units are designed to operate with high water temperature (14/20 °C) despite being possible, with a dedicated option, to operate with conventional water temperature (7/12 °C).

Versions

  • WOPU/C - Underfloor air discharge
  • WOPU/U - Underfloor air discharge
  • WOPU/E - Underfloor air discharge
  • WOPU/D - Underfloor air discharge
  • BFU - Fan module for underfloor version
  • BFM - Fan module for above the floor version

Power range

  • 117-282 kW
  • 33,0-80,0 Ton

Factory fitted accessories

  • SW Low water temperature operation 7/12°C
  • DPS Double power supply
  • AT Constant air flow regulation control
  • AT/P Constant available static pressure regulation control
  • PF Differential pressure switch filters control
  • ES Electrical heater with step regulation
  • UMI Electrodes steam humidifier
  • SA Water alarm sensor
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISS SNMP protocol, Ethernet port
  • MV 2 way modulating valve
  • MVP 2 way modulating and balancing valve with flow meter, pressure independent
  • FME Flow meter
  • EM Energy meter
  • RE Adjustable minimum/maximum voltage and phase control relay
  • OW Outlet water temperature sensor

Loose accessories

  • MP Condensate drain pump
  • MP/U Condensate and humidifier drain pump
  • SB Fire sensor
  • SC Smoke sensor
  • CR Remote control panel
  • ZP Adjustable baseframe with shock absorbers (mod. B only)
  • BA Top vertical intake plenum with F7 efficiency filter (mod. B only)
  • BU Top frontal intake plenum with grid
  • BV Top discharge/intake plenum with damper