free cooling.png

CRE-FC 6205÷121060

Aircooled liquid Chillers Free-Cooling with axial fans, Scroll compressors and plate exchanger

_montair_icon_cooling_only.png _montair_Scroll_2015.png _montair_icon_Axial_fans_2015.png _montair_icon_plate_2015.png _montair_FC_2015.png _montair_icon_refrigerant_R410A_14.png _montair_icon_refrigerant_R452B.png icon_refrigerant_R454B.png

The liquid Chillers of the CRE-FC 6205÷121060 series, with R410A refrigerant, provide advanced technology, flexible and reliable, through an intelligent control module which optimizes the operating times and the powers delivered by the Scroll compressors, according to the needs of data centre systems, where the production of chilled water is required in continuous service throughout the year. During the cold months, in FREE-COOLING operating mode, the liquid returning from the system is cooled directly, by way of the forced convection of outside air through the condensing coil, thus reducing the energy required for the Scroll compressors operation that the units are equipped with. A system of 3-way valves, controlled by the electronic microprocessor controller that manages the entire unit, can, depending on outside air temperature, operate in the CHILLER, FREE-COOLING or MIXED (CHILLER and FREE-COOLING at the same time) mode. CRE-FC 6205÷121060 allows the reduction of inrush currents generated, the elimination of inertial accumulation tanks and an excellent silent functioning, as the fans adjust their speed to the actual load of the system, providing great benefits especially at night.
Units are featured as standard with an electronic proportional device that ensures efficient continuous functioning of the unit with outside air temperature down to –20 °C.

Versions

  • CRE-FC - Cooling only

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tubes and aluminium finned coils combined with FREE-COOLING coils.
  • Evaporator AISI 316 stainless steel braze welded plates type with two independent circuits on the refrigerant side and one on the water side, complete with water differential pressure switch.
  • Cooling circuit shut-off valve on liquid line in 8330÷121060 models.
  • Electronic expansion valve.
  • Electronic high and low pressure gauges.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses or magnetothermic switches, thermal protection relays for compressors and thermocontacts for fans.
  • Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, high and low pressure transducers on cooling circuit and an electrical heater on electrical board.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • DPS Double power supply
  • SL Unit silencement
  • RFM Cooling circuit shut-off valve on discharge line
  • EC EC Inverter fans
  • ECH EC Inverter fans with high available static pressure
  • TX Coil with pre-coated fins
  • PS Single circulating pump
  • PSI Inverter single circulating pump
  • PD Double circulating pump
  • PDI Inverter double circulating pump
  • SS Soft start
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet TCP/IP protocol, Ethernet port
  • ISL LonWorks protocol, FTT-10 serial interface
  • ISS SNMP protocol, Ethernet port
  • IAV Remote set-point, 0-10 V signal
  • IAA Remote set-point, 4-20 mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input

Loose accessories

  • MN High and low pressure gauges
  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
6205623062556280833083408375104101045512510125601261512680127701286012950121060
CoolingCooling capacity (1)kW2002212462733073383734094555035526206977798719641032
Absorbed power (1)kW7077788796108116130145159175204239272304332366
EER (1)2,862,873,153,143,203,133,223,153,143,163,153,042,922,862,872,902,82
Cooling (EN14511)SEPR (2)5,045,035,025,055,015,065,025,515,535,525,545,565,585,555,535,525,51
Free-Cooling cycleAir temperature (3)°C-2,0-2,8-2,5-0,2-2,7-3,5-1,0-2,0-1,0-2,2-2,7-3,0-3,5-2,5-0,10,1-0,4
Absorbed power (3)kW7,07,010,510,514,014,014,014,017,517,517,517,521,024,528,031,531,5
CompressorQuantity3+33+33+33+34+44+44+45+55+56+66+66+66+66+66+66+66+6
Refrigerant circuits22222222222222222
Capacity steps44444446688888888
Water flowl/s10,3211,4012,6914,0815,8417,4419,2521,1023,4825,9528,4831,9935,9640,2044,9449,7453,25
Pressure dropskPa77921189080748170878795105111125111120124
Water connectionsDN100100100100100100100100100125125125150150150150150
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA165182199216248266285301352389415484561637714763816
Max. starting currentA28831536638338143345243351955658265873684592210241077
Unit with pumpPump available static pressurekPa190195155180175160160165140185170150225190190150145
Water connectionsDN100100100100100100100100100125125125150150150150150
Sound pressureSTD version (4)dB(A)7070717373737475747476787879787879
With SL accessory (4)dB(A)6867687070707172717174757575757576
WeightsTransport weightkg21752185236024352990302032203510392041804220506052405830688074107530
Operating weightkg23102320250026303190322034703770425045204560546056506320760082208340

Dimensions

6205623062556280833083408375104101045512510125601261512680127701286012950121060
LSTDmm4000400040004000500050005000500062006200620072007200840096001060010600
WSTDmm22002200220022002200220022002200220022002200220022002200220022002200
HSTDmm23602360236023602360236023602360236023602360236023602360236023602360

Notes

  • 1 Chilled water (with ethylene glycol at 30%) from 18 to 13 °C, ambient air temperature 35 °C.
  • 2 Efficienza energetica stagionale di raffreddamento di processo ad alta temperatura secondo il Regolamento UE n. 2016/2281.
  • 3 Ambient air temperature at which the cooling capacity indicated in point (1) is reached.
  • 4 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.