CRE 2050÷4190

AIRCOOLED LIQUID CHILLERS WITH AXIAL FANS, SCROLL COMPRESSORS AND PLATE EXCHANGER

_montair_icon_cooling_only.png _montair_Scroll_2015.png _montair_icon_Axial_fans_2015.png _montair_icon_plate_2015.png _montair_icon_refrigerant_R410A_14.png _montair_icon_refrigerant_R452B.png icon_refrigerant_R454B.png

The liquid Chillers of the CRE 2050÷4190 series, with R410A refrigerant, are specifically designed for medium size data centres.
Equipped with axial fans, Scroll compressors and plate exchanger, even in the super silent version, these units can be completed by a hydraulic circuit with tank, with pump, or with tank and pump. A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Units are featured as standard with an electronic proportional device that ensures efficient continuous functioning of the unit with outside air temperature down to –20 °C.

Versions

  • CRE - Cooling only
  • CRE/SSL - Super silenced cooling only

Power range

  • 48.0-169 kW
  • 14.0-48.0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tubes and aluminium finned coil.
  • Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side in 2050÷3135 models; with two independent circuits on the refrigerant side and one on the water side in 4150÷4190 models, complete with water differential pressure switch.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
  • Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, high and low pressure transducers on cooling circuit and an electrical heater on electrical board.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • IM Automatic circuit breakers
  • SL Unit silencement
  • TE Electronic expansion valve
  • RFM Cooling circuit shut-off valve on discharge line
  • RFL Cooling circuit shut-off valve on liquid line
  • EC EC Inverter fans
  • ECH EC Inverter fans with high available static pressure
  • TX Coil with pre-coated fins
  • SI Inertial tank
  • PS Single circulating pump
  • PD Double circulating pump
  • SS Soft start
  • IS Modbus RTU protocol, RS485 serial interface

Loose accessories

  • MN High and low pressure gauges
  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
2050205520702080209031053120313541504190
CoolingCooling capacity (1)kW48,255,465,073,182,196,9111125141169
Absorbed power (1)kW15,117,119,622,625,630,034,039,343,349,9
EER (1)3,193,243,323,233,213,233,263,183,263,39
Cooling (EN14511)Cooling capacity (1)kW47,855,064,672,781,796,4111124141168
Absorbed power (1)kW15,417,520,023,126,030,634,540,044,050,7
EER (1)3,103,153,243,153,143,153,213,113,213,31
SEPR (2)5,115,145,195,155,145,115,105,185,095,10
CompressorQuantity2222233344
Refrigerant circuits1111111122
Capacity steps2222233344
EvaporatorWater flowl/s2,302,653,113,493,924,635,305,976,748,07
Pressure dropskPa46494548425947514443
Water connections"G1 ½"1 ½"1 ½"1 ½"1 ½"2 ½"2 ½"2 ½"2 ½"2 ½"
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA43455559707890108116136
Max. starting currentA166168177190235203222269247304
Unit with tank and pumpPump available static pressurekPa140130130115135160165155150140
Tank water volumel400400400400400400400400600600
Water connections"G2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"
Sound pressureSTD version (3)dB(A)61---6464656667676767
With SL accessory (3)dB(A)59---6262636465656565
SSL version (3)dB(A)575760606162636363---
WeightsTransport weight (4)kg595---663682791878927103611351374
Operating weight (4)kg600---670690800890940105011501390

Dimensions

2050205520702080209031053120313541504190
LSTDmm2350235023502350235023502350235035503550
SSLmm235023502350235023502350355035503550---
WSTD/SSLmm1100110011001100110011001100110011001100
HSTD/SSLmm1920192019201920222022202220222022202220

Notes

  • 1 Chilled water from 18 to 13 °C, ambient air temperature 35 °C.
  • 2 Efficienza energetica stagionale di raffreddamento di processo ad alta temperatura secondo il Regolamento UE n. 2016/2281.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • 4 Unit without tank and pump.
  • N.B. (1) Weights of SSL version are specified on technical brochure.