inverter scroll.png

microchannel.png

CREI-E 2060÷4210

A CLASS energy efficiency aircooled liquid Chillers with axial fans, Inverter Scroll compressors, Microchannel condensing coil and plate exchanger

_montair_icon_cooling_only.png _montair_Scroll_inverter_2015.png _montair_icon_Axial_fans_2015.png _montair_icon_plate_2015.png _montair_icon_microchannel_2015.png ICONA_A.png _montair_icon_refrigerant_R410A_14.png

The A CLASS energy efficiency liquid Chillers of the CREI-E 2060÷4210 series, with R410A refrigerant, are specifically designed for medium size data centres.
They are equipped with axial fans, Inverter Scroll compressors, Microchannel condensing coils and plate exchanger, even in the super silent version. The Microchannel condensing coils ensure an high efficiency (high EER), having a better heat exchange than traditional coils. A better efficiency at partial loads (SEPR/ESEER/IPLV) is guaranteed by the Inverter control on Scroll compressor. Furthermore, Inverter control is also available on circulating pump and fans (EC) for a further efficiency improvement. A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Units are featured as standard with an electronic proportional device that ensures efficient continuous functioning of the unit with outside air temperature down to –20 °C.

Versions

  • CREI-E - Cooling only
  • CREI-E/SSL - Super silenced cooling only

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • DC INVERTER Scroll and ON-OFF Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of aluminium MICROCHANNEL coil.
  • Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side in 2060÷2150 models; with two independent circuits on the refrigerant side and one on the water side in 4180÷4210 models, complete with water differential pressure switch.
  • Electronic expansion valve.
  • Electronic high and low pressure gauges.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
  • Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, high and low pressure transducers on cooling circuit and an electrical heater on electrical board.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • IM Automatic circuit breakers
  • SL Unit silencement
  • RFM Cooling circuit shut-off valve on discharge line
  • RFL Cooling circuit shut-off valve on liquid line
  • EC EC Inverter fans
  • ECH EC Inverter fans with high available static pressure
  • TXB Coil with epoxy treatment
  • PS Single circulating pump
  • PSI Inverter single circulating pump
  • PD Double circulating pump
  • PDI Inverter double circulating pump
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet TCP/IP protocol, Ethernet port
  • ISL LonWorks protocol, FTT-10 serial interface
  • ISS SNMP protocol, Ethernet port
  • IAV Remote set-point, 0-10 V signal
  • IAA Remote set-point, 4-20 mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input

Loose accessories

  • MN High and low pressure gauges
  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
2060206520752085210021152130215041804210
CoolingCooling capacity (1)kW56,965,875,687,099,9112130150175206
Absorbed power (1)kW15,818,421,424,728,231,936,241,949,157,7
EER (1)3,603,583,533,523,543,513,593,583,563,57
Cooling (EN14511)Cooling capacity (1)kW56,565,475,286,499,2112129149174206
Absorbed power (1)kW16,218,821,825,328,932,636,942,849,958,5
EER (1)3,493,473,453,423,433,433,503,483,493,51
SEPR (2)5,655,805,655,605,635,655,725,605,615,56
CompressorQuantity2222222244
Refrigerant circuits1111111122
Capacity stepsSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessStepless
EvaporatorWater flowl/s2,723,143,614,164,775,356,217,178,369,84
Pressure dropskPa54524253645247594440
Water connections"G1 ½"1 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA4044515667768694120136
Max. starting currentA120122171175186241221225237254
Unit with pumpPump available static pressurekPa130120125100100160160130130120
Water connections"G2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"2 ½"
Sound pressureSTD version (3)dB(A)62646565666767686767
With SL accessory (3)dB(A)60616363646565666565
SSL version (3)dB(A)5759606061616162------
WeightsTransport weightkg5846537127217308171036104513791424
Operating weightkg5906607207307408301050106014001450

Dimensions

2060206520752085210021152130215041804210
LSTDmm2350235023502350235035503550355047004700
SSLmm23502350235035503550355047004700------
WSTD/SSLmm1100110011001100110011001100110011001100
HSTDmm1920222022202220222019202220222022202220
SSLmm19202220222019201920222022202220------

Notes

  • 1 Chilled water from 18 to 13 °C, ambient air temperature 35 °C.
  • 2 Efficienza energetica stagionale di raffreddamento di processo ad alta temperatura secondo il Regolamento UE n. 2016/2281.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of SSL version are specified on technical brochure.