DOP 0028÷0093

CHILLED WATER Dual coil UNITS WITH EC INVERTER PLUG-FAN

_montair_CHILLED_H2O_2015.png _montair_DUAL_COIL_2015.png _montair_EC_plug_fan_inverter_2015.png _montair_EC_plug_fan_inverter_HIGH_ESP2015.png _montair_HT_2015.png

Dual Coil units with two independent cooling circuits, both with chilled water. The circuits are connected with two watercooled or aircooled liquid Chillers, with Free-Cooling technology too. The two circuits are separated with nonsimultaneous start-up, for back-up operation.
The DOP range is equipped with EC Inverter Plug-Fans; High Head fans are available as accessories.
The EC Inverter Plug-Fans allow fuel consumption at partial loads to be reduced by up to 61% compared to radial fans, modulating the power consumption according to the required thermal load.
The DOP range is available in two air discharge versions: DOPT with top air discharge and DOPB with bottom air discharge.
Unit supervision is developed by means of Modbus RTU protocol over RS485
serial interface as standard configuration. Other communication protocols and
interfaces are available as option.

Versions

  • DOPT/C - Top air discharge and frontal intake
  • DOPT/U - Top air discharge and frontal intake
  • DOPT/E - Top air discharge and frontal intake
  • DOPT/D - Top air discharge and frontal intake
  • DOPB/C - Bottom air discharge and upper intake
  • DOPB/U - Bottom air discharge and upper intake
  • DOPB/E - Bottom air discharge and upper intake
  • DOPB/D - Bottom air discharge and upper intake

Power range

  • 29.0-93.0 kW
  • 8.1-26.0 Ton

Factory fitted accessories

  • AP High ESP fans
  • HT High water temperature operation 13/18°C
  • DPS Double power supply
  • AR Air renewal inlet with filter
  • AT Constant air flow regulation control
  • AT/P Constant available static pressure regulation control
  • PF Differential pressure switch filters control
  • ES Electrical heater with step regulation
  • WS2 Hot water coil with 3-Way valve
  • UMI Electrodes steam humidifier
  • SA Water alarm sensor
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISS SNMP protocol, Ethernet port
  • RE Adjustable minimum/maximum voltage and phase control relay

Loose accessories

  • MP Condensate drain pump
  • MP/U Condensate and humidifier drain pump
  • SB Fire sensor
  • SC Smoke sensor
  • CR Remote control panel
  • ZP Adjustable baseframe with shock absorbers (mod. B only)
  • ZA Adjustable baseframe with shock absorbers and deflector (mod. B only)
  • DL Bottom plenum for side connections (mod. T only)
  • BA Top vertical intake plenum with F7 efficiency filter (mod. B only)
  • BD Top frontal discharge plenum with grid (mod. T only)
  • DM Bottom frontal discharge plenum with grid (mod. B only)
  • BV Top discharge/intake plenum with damper
00280038005600770093
PRIMARY COOLING circuit performancesTotal cooling capacity (1)kW28,538,155,876,693,0
Sensible cooling capacity (1)kW28,535,851,770,886,0
SHR (1)%100%94%93%92%92%
Water flow (1)l/s1,361,822,673,664,44
Total pressure drops (1)kPa2424333338
SECONDARY COOLING circuit performancesTotal cooling capacity (1)kW28,538,155,876,693,0
Sensible cooling capacity (1)kW28,535,851,770,886,0
SHR (1)%100%94%93%92%92%
Water flow (1)l/s1,361,822,673,664,44
Total pressure drops (1)kPa2424333338
Primary cooling circuit performances with HT accessoryTotal cooling capacity (2)kW23,129,742,958,571,2
Sensible cooling capacity (2)kW23,129,742,958,571,2
SHR (2)%100%100%100%100%100%
Water flow (2)l/s1,101,422,052,793,40
Total pressure drops (2)kPa2323292731
Secondary cooling circuit performances with HT accessoryTotal cooling capacity (2)kW23,129,742,958,571,2
Sensible cooling capacity (2)kW23,129,742,958,571,2
SHR (2)%100%100%100%100%100%
Water flow (2)l/s1,101,422,052,793,40
Total pressure drops (2)kPa2323292731
Fan sectionFans11223
Air flow (3)m³/h97009700138001880022800
Max. available static pressure - STD fansPa290200400230340
Max. available static pressure - High ESP fansPa480400550400510
FiltersTipoM5M5M5M5M5
Electrical characteristicsPower supplyV/Ph/Hz400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50
Sound pressureDOPT - Top Air Discharge version (4)dB(A)6061586461
DOPB - Bottom Air Discharge version (4)dB(A)5556535956
ACCESSORIES & ADDITIONAL SECTIONSACCESSORIES & ADDITIONAL SECTIONS     
Electrical heatingSteps33333
Electrical powerkW13,513,516,522,527,0
Hot water coilHeating capacity (5)kW26,026,035,851,462,9
Water flow (5)l/s1,241,241,712,463,01
Total pressure drops (5)kPa4040444848
Electrodes steam humidifierNominal steam productionkg/h8881515
Nominal powerkW6,06,06,011,311,3
WeightsTransport weight DOPT - Top Air Dischargekg473499562752891
Transport weight DOPB - Bottom Air Dischargekg491517592782927
Operating weight DOPT - Top Air Dischargekg453477540719858
Operating weight DOPB - Bottom Air Dischargekg471495570749894

Dimensions

00280038005600770093
DimensionsLmm13501350175022252625
Wmm890890890890890
Hmm19801980198019801980

Notes

  • 1 Ambient air temperature 24°C - R.H. 50%, water temperature 7°C / 12°C.
  • 2 Ambient air temperature 27°C - R.H. 50%, water temperature 13°C / 18°C.
  • 3 Air flow calculated with Available Static Pressure of 20 Pa.
  • 4 Sound pressure level calculated in free field conditions at 1,5 m height and 2 m distance. According to ISO 3744.
  • 5 Ambient air temperature 20°C, water temperature 45°C / 40°C.