XIPR-ER 1010÷1035
DIRECT EXPANSION CONDITIONING UNITS IN RACK ENCLOSURE + REDUNDANCY
It is also possible to achieve a fully redundant system XIPR-ER by coupling the rack with two direct expansion cooling modules. These systems are flexible, easy to be implemented and they are the perfect solution for different applications such as micro data centers, high density servers, EDGE computing, IOT applications, 5G devices. The two modules can operate in a Master/Slave configuration with one unit working and one unit in stand-by with rotation of the stand-by unit on time basis.
Versions
- XIPR-ER/C - Enclosure type with redundancy 1200 mm
- R6 - Rack for Enclosure 600 x 1200 x 42U
- R8 - Rack for Enclosure 800 x 1200 x 42U
Power range
- 13.0-43.0 kW
Accessories
Factory fitted accessories
- MP Condensate drain pump
- SA Water alarm sensor
- IS Modbus RTU protocol, RS485 serial interface
- IST Modbus TCP/IP protocol, Ethernet port
- ISB BACnet MSTP protocol, RS485 serial interface
- ISBT BACnet IP protocol, Ethernet port
- ISS SNMP protocol, Ethernet port
- STT Remote air temperature sensors
- TCF Refrigerant connections from the top
Loose accessories
- CR Remote control panel
Technical data
1010 | 1015 | 1025 | 1035 | |||
Performances | Total Cooling Capacity - Max (1) | kW | 12,8 | 18,1 | 27,3 | 43,0 |
Total Cooling Capacity - min (1) | kW | 6,5 | 7,6 | 11,9 | 18,2 | |
Sensible cooling capacity - Max. (1) | kW | 12,8 | 18,1 | 27,3 | 43,0 | |
Sensitive cooling capacity - min (1) | kW | 6,5 | 7,6 | 11,9 | 18,2 | |
SHR - Max (1) | % | 100 | 100 | 100 | 100 | |
SHR - min (1) | % | 100 | 100 | 100 | 100 | |
Fans | Tipo | EC Plug-Fans | EC Plug-Fans | EC Plug-Fans | EC Plug-Fans | |
Fans | n° | 3 | 3 | 4 | 6 | |
Air Flow Rate - Max | m³/h | 2500 | 3000 | 4000 | 5800 | |
Air flow - min | m³/h | 1250 | 1500 | 2000 | 2900 | |
Fan energy consumption - Max | kW | 0,18 | 0,31 | 0,44 | 0,70 | |
Fan energy consumption - min | kW | 0,03 | 0,05 | 0,07 | 0,12 | |
Power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | |
Weight indoor unit | Weight | kg | 198 | 198 | 207 | 217 |
Weight - Rack 600 | kg | 175 | 175 | 175 | 175 | |
Weight - Rack 800 | kg | 205 | 205 | 205 | 205 | |
COMBINATION WITH CONDENSING UNIT | 2x1010 | 2x1015 | 2x1025 | 2x1035 |
Dimensions
1010 | 1015 | 1025 | 1035 | |||
Indoor unit dimensions | L (2) | mm | 300+300+Rack | 300+300+Rack | 300+300+Rack | 300+300+Rack |
W (3) | mm | 1200 | 1200 | 1200 | 1200 | |
H | mm | 2073 (42 U) | 2073 (42 U) | 2073 (42 U) | 2073 (42 U) |
Notes
- 1 Return air 46°C - 20% rh and 35°C outdoor temperature.
- 2 Rack 600 mm or Rack 800 mm width.
- 3 Nominal dimension (overall dimension 1250mm).
Documents
- Product overview (IT) _montair_close_control_over_2023_ITA_w.pdf
- Product overview (EN) _montair_close_control_over_2023_ENG_w_mLQrzHm.pdf
- Product overview (ES) _montair_close_control_over_2023_SPA_w.pdf
- Product guides (IT) _montair_close_control_product_guide_2023_ITA_w_TdrD7Bl.pdf
- Product guides (EN) _montair_close_control_product_guide_2023_ENG_w_mV3CzWD.pdf
- Commercial leaflets _montair_IN-ROW_2022_w.pdf
- Technical brochures 06_IN_ROW__IN_RACK_mtb_229_JZFJNl0.pdf