WOPR-ER 0015÷0030

HIGH PERFORMING CHILLED WATER IN RACK ENCLOSURE + REDUNDANCY CONDITIONING UNITS

_icona_montair_chilled-water.png _icona_montair_EC-Inverter-Plug-fan.png _icona_montair_HT.png

It is also possible to achieve a fully redundant system WOPR-ER by coupling the rack with two chilled water cooling modules. These systems are flexible, easy to be implemented and they are the perfect solution for different applications such as micro data centers, high density servers, EDGE computing, IOT applications, 5G devices. The two modules can operate in a Master/Slave configuration with one unit working and one unit in stand-by with rotation of the stand-by unit on time basis.
These units are equipped with EC Inverter Plug-Fans with backward curved blades and a cooling coil optimised to operate with high inlet water temperature and a large ∆T. Variations in heat load are controlled by the simultaneous action of a 2-way or 3-way modulation valve and automatic fan speed control by means of microprocessor-controlled control logic and an advanced user interface.

Versions

  • WOPR-ER - Enclosure type with Redundancy - 1200 mm

Power range

  • 21.0-43.0 kW
  • 5.9-12.0 Ton

Factory fitted accessories

  • R6 Rack for Enclosure 600 x 1200 x 42U
  • R8 Rack for Enclosure 800 x 1200 x 42U
  • MP Condensate drain pump
  • DPS Double power supply
  • SA Water alarm sensor
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISS SNMP protocol, Ethernet port
  • MVP 2 way modulating and balancing valve with flow meter, pressure independent
  • MQ 3-Way modulating valve
  • OW Outlet water temperature sensor
  • TCI Hydraulic connections from the top

Loose accessories

  • CR Remote control panel
0015002000250030
PerformancesTotal cooling capacity (1)kW20,628,234,342,7
Sensible cooling capacity (1)kW20,628,234,342,7
SHR (1)%1111
Fans3346
Air flowm³/h3000400054005800
Fan energy consumptionkW0,270,390,520,65
Water flow (1)l/s0,821,121,371,70
Pressure drops (1)kPa49,039,346,061,1
Power supplyV/Ph/Hz230/1/50230/1/50230/1/50230/1/50

Dimensions

0015002000250030
Indoor unit dimensionsL (2)mm300+300+Rack300+300+Rack300+300+Rack300+300+Rack
W (3)mm1200120012001200
Hmm2073 (42 U)2073 (42 U)2073 (42 U)2073 (42 U)
Weight indoor unitWeightkg200206211216
Weight - Rack 600kg175175175175
Weight - Rack 800kg205205205205

Notes

  • 1 Return air 46°C - 20% rh and 14/20°C water temperature.