LRE/TTY/FC

LRE/TTY/FC - LOGICA AIRCOOLED LIQUID CHILLERS FREE-COOLING WITH TURBOCOR COMPRESSORS AND EC INVERTER FANS

_montair_icon_EC_Axial_fans_2015.png _montair_icon_turbocor_14.png _montair_icon_flooded_shell_2015.png _montair_FC_2015.png _montair_icon_refrigerant_R134a_14.png icon_refrigerant_R513A.png

LRE/TTY/FC - LOGICA AIRCOOLED LIQUID CHILLERS FREE-COOLING WITH TURBOCOR COMPRESSORS AND EC INVERTER FANS

Versions

  • LRE/TTY/FC - Cooling only

Features

  • 7 sizes with cooling capacity from 243 to 657 kW (from 69 to 187 TON)
  • EC Inverter axial fans
  • Turbocor compressors
  • Flooded shell and tube exchanger
  • Double circulating pump
  • FREE-COOLING
  • On request, units can be supplied with R513A refrigerant
1250-11300-11400-11500-12720-12500-22720-2
PerformancesCooling capacity (1)kW243277331504657504657
Absorbed power (1)kW58,165,579,5120174118174
EER (1)4,184,234,164,213,784,263,78
Power supplyV/Ph/Hz400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50400 / 3 / 50
Free Cooling 100%Air temperature (2)°C9,512,09,09,011,099,011,0
Absorbed power (2)kW10,810,810,818,021,618,021,6
CompressorsQuantity1111222
Circuits1111122
Capacity stepsSteplessSteplessSteplessSteplessSteplessSteplessStepless
Water circuit.Water flowl/s10,812,314,622,329,122,329,1
Sound pressureSTD version (3)dB(A)61616162626362

Dimensions

Notes

  • 1 Chilled water (with ethylene glycol at 30%) from 20 to 15°C, ambient air temperature 35°C.
  • 2 Ambient air temperature at wich the cooling capacity indicated in point (1) is reached.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) The nominal inlet/outlet water temperature at note (1) is 3 degrees lower than nominal inlet/outlet water temperature on cooling door to take into account the presence of LPS Leak Prevention System.