LRE/Y
LRE/Y - LOGICA AIRCOOLED LIQUID CHILLERS WITH SCREW COMPRESSORS, MICROCHANNEL CONDENSING COILS AND EC INVERTER FANS
LRE/Y - LOGICA AIRCOOLED LIQUID CHILLERS WITH SCREW COMPRESSORS, MICROCHANNEL CONDENSING COILS AND EC INVERTER FANS
Versions
- LRE/Y - Cooling only
- LRE/Y/SSL - Super silenced cooling only
- LRE - Cooling only
- LRE/SSL - Super silenced cooling only
Features
- 4 sizes with cooling capacity from 319 to 803 kW (from 91 to 228 TON)
- EC Inverter axial fans
- Screw compressors (Inverter Screw also available on request)
- Microchannel condensing coils
- Shell and tube exchanger
- Double circulating pump
- On request, units can be supplied with R513A refrigerant
Technical data
2300 | 2450 | 2550 | 2800 | 6250 | 6300 | 8400 | 10500 | 12750 | |||
Performances | Cooling capacity (1) | kW | 319 | 438 | 561 | 803 | 248 | 299 | 394 | 491 | 763 |
Absorbed power (1) | kW | 79,4 | 112 | 146 | 201 | 82,7 | 92,5 | 118 | 154 | 254 | |
EER (1) | 4,02 | 3,92 | 3,84 | 4,00 | 3,00 | 3,23 | 3,33 | 3,19 | 3,01 | ||
Power supply | V/Ph/Hz | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | 400 / 3 / 50 | |
Compressors | Quantity | n° | 2 | 2 | 2 | 2 | 6 | 6 | 8 | 10 | 12 |
Circuits | n° | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |
Capacity steps | n° | Stepless | Stepless | Stepless | Stepless | 6 | 6 | 8 | 10 | 10 | |
Water circuit. | Water flow | l/s | 15,3 | 20,9 | 26,8 | 38,4 | 11,9 | 14,3 | 18,8 | 23,5 | 36,5 |
Sound pressure | STD version (2) | dB(A) | 76 | 77 | 78 | 79 | 66 | 69 | 70 | 69 | 73 |
With SL accessory (2) | dB(A) | 74 | 75 | 76 | 77 | 63 | 66 | 66 | 66 | 70 | |
SSL version (2) | dB(A) | 68 | 69 | 70 | 71 | 59 | 61 | 60 | 61 | 65 |
Dimensions
Notes
- 1 Chilled water from 20 to 15°C, ambient air temperature 35°C.
- 2 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- N.B. (1) The nominal inlet/outlet water temperature at note (1) is 3 degrees lower than nominal inlet/outlet water temperature on cooling door to take into account the presence of LPS Leak Prevention System.
Documents
- Product overview (IT) _montair_close_control_over_2023_ITA_w.pdf
- Product overview (EN) _montair_close_control_over_2023_ENG_w_mLQrzHm.pdf
- Product overview (ES) _montair_close_control_over_2023_SPA_w.pdf
- Product guides (IT) _montair_close_control_product_guide_2023_ITA_w_TdrD7Bl.pdf
- Product guides (EN) _montair_close_control_product_guide_2023_ENG_w_mV3CzWD.pdf