CRW-TRH 1340/1÷62120/1
A CLASS ENERGY EFFICIENCY WATERCOOLED LIQUID CHILLERS WITH TURBOCOR (MAGNETIC LEVITATION) COMPRESSORS AND FLOODED SHELL AND TUBE EXCHANGERS FOR COOLING TOWER OPERATION
The innovative CRW-TRH 1340/1÷62120/1 units for cooling tower operation, featuring A CLASS energy efficiency and HFO-R1234ze refrigerant, are designed to provide an effective solution to highly selective system needs. The latest generation refrigerant HFO-R1234ze, with GWP<1 (Global warming Potential), is the most environmentally sustainable refrigerant on the market, and meets the strictest international environmental regulations. Furthermore, thanks to Turbocor compressors, the units perform with top efficiency at partial loads, low inrush currents, an excellent silent functioning and reduced weight.
Using TURBOCOR dynamic partial-load oil-free magnetic levitation compressors, managed by the TURBOSOFT self-adaptive electronic control and flooded shell and tube evaporators, provide high energy performance, with unbeatable SEPR/ESEER/IPLV values, with minimum water content, and an excellent silent functioning. Compared to traditional Screw compressor units, CRW-TRH 1340/1÷62120/1 units have low operational costs during their entire use, with a savings that can even reach 50%. Besides, the units are equipped with the WEB MONITORING system, for remotely managing and monitoring the units by means of GPRS/EDGE/3G/TCP-IP communication protocol. The users enabled to use this service can, by a dedicated Web page, access Monitoring, Management and Statistics activities.
Versions
- CRW-TRH - Cooling only for cooling tower
Features
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Semi-hermetic centrifugal compressors with dual Turbocor turbine, oil free, magnetic rising rotor, thermal protection, continuous capacity adjustment system thanks to built-in INVERTER, automatic anti-cavitation system. The power circuit of the compressor is fitted with a set of electrolytic condensers to control the rising in the event of a power failure, reactor for the power factor correction, EMI filter for electromagnetic compatibility.
- Shell and tube type condenser, with easily removable cast iron heads to enable access for maintenance operations.
- High efficiency flooded shell and tube type evaporator, with one circuit on the refrigerant side and one on the water side, complete with water differential pressure switch.
- Cooling circuit shut-off valves on suction, discharge and liquid line.
- Electronic expansion valve.
- Electronic high and low pressure gauges.
- HFO-R1234ze refrigerant.
- Electrical board includes: main on-off switch with door lock, fuses, electronic/digital overload device to protect the compressors, interface relay and terminals for external connections.
- TURBOSOFT control and regulation system, equipped with RS485 serial interface, can be supplied with an optional Web Monitoring device for remote monitoring via GPRS/EDGE/3G/TCP-IP network.
Accessories
Factory fitted accessories
- IM Automatic circuit breakers
- DPS Double power supply
- TS Touch Screen Interface
- WM Web Monitoring - Wireless remote monitoring (GPRS/EDGE/3G/TCP-IP)
- IST Modbus TCP/IP protocol, Ethernet port
- ISB BACnet MSTP protocol, RS485 serial interface
- ISBT BACnet TCP/IP protocol, Ethernet port
- ISL LonWorks protocol, FTT-10 serial interface
- ISS SNMP protocol, Ethernet port
- IAV Remote set-point, 0-10 V signal
- IAA Remote set-point, 4-20 mA signal
- IAS Remote signal for second set-point activation
- IDL Demand limit from digital input
- CP Potential free contacts
Loose accessories
- MN High and low pressure gauges
- CR Remote control panel
- AG Rubber shock absorbers
- AM Spring shock absorbers
- FL Flow switch
Technical data
1340/1 | 2700/1 | 31070/1 | 41420/1 | 51760/1 | 62120/1 | |||
Cooling | Cooling capacity (1) | kW | 376 | 739 | 1121 | 1494 | 1851 | 2226 |
Absorbed power (1) | kW | 58 | 111 | 174 | 231 | 279 | 335 | |
EER (1) | 6,48 | 6,66 | 6,44 | 6,47 | 6,63 | 6,64 | ||
Cooling (EN14511) | Cooling capacity (1) | kW | 374 | 736 | 1116 | 1489 | 1843 | 2217 |
Absorbed power (1) | kW | 61,7 | 116 | 183 | 242 | 291 | 350 | |
EER (1) | 6,06 | 6,34 | 6,09 | 6,16 | 6,32 | 6,34 | ||
SEPR (2) | 9,40 | 9,54 | 9,71 | 10,48 | 10,72 | 10,74 | ||
Compressor | Quantity | n° | 1 | 2 | 3 | 4 | 5 | 6 |
Refrigerant circuits | n° | 1 | 1 | 1 | 1 | 1 | 1 | |
Capacity steps | n° | Stepless | Stepless | Stepless | Stepless | Stepless | Stepless | |
Evaporator | Water flow | l/s | 17,96 | 35,31 | 53,56 | 71,38 | 88,44 | 106 |
Pressure drops | kPa | 62 | 62 | 62 | 46 | 70 | 67 | |
Water connections | DN | 100 | 125 | 150 | 150 | 200 | 200 | |
Condenser | Water flow | l/s | 20,74 | 40,61 | 61,87 | 82,42 | 102 | 122 |
Pressure drops | kPa | 66 | 65 | 66 | 67 | 71 | 68 | |
Water connections | DN | 100 | 125 | 150 | 150 | 200 | 200 | |
Electrical characteristics | Power supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. running current | A | 150 | 300 | 450 | 600 | 750 | 900 | |
Max. starting current | A | 5 | 155 | 305 | 455 | 605 | 755 | |
Sound pressure | STD version (3) | dB(A) | 72 | 74 | 76 | 76 | 77 | 78 |
Weights | Transport weight | kg | 1798 | 2837 | 3924 | 6408 | 7741 | 11474 |
Operating weight | kg | 1930 | 3100 | 4340 | 7120 | 8780 | 13140 |
Dimensions
1340/1 | 2700/1 | 31070/1 | 41420/1 | 51760/1 | 62120/1 | |||
L | STD | mm | 3400 | 3400 | 3450 | 4550 | 5500 | 6500 |
W | STD | mm | 1100 | 1150 | 1800 | 1800 | 1800 | 1800 |
H | STD | mm | 1800 | 1950 | 2050 | 2100 | 2100 | 2150 |
Notes
- 1 Chilled water from 18 to 13 °C, water temperature at the condenser from 30 to 35 °C.
- 2 Efficienza energetica stagionale di raffreddamento di processo ad alta temperatura secondo il Regolamento UE n. 2016/2281.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.