TOP 1025÷4118

AIR COOLED DIRECT EXPANSION DUAL FLUID UNITS WITH SCROLL COMPRESSORS AND EC INVERTER PLUG-FANS

_icona_montair_DF.png _icona_montair_scroll.png _icona_montair_EC-Inverter-Plug-fan.png _icona_montair_EC-Inverter-Plug-fan_HESP.png _icona_montair_XT.png _icona_clint_refrigerant_R410A_2024.png

Dual Fluid unit with direct expansion, air-condensation and double circuit: one with direct expansion and air-condensing, and one with chilled water.
The two circuits are separate and with non-simultaneous start-up, for internal back-up.
The TOP range is equipped with EC Inverter Plug-Fans; High Head fans are available as accessories.
The EC Inverter Plug-Fans allow fuel consumption at partial loads to be reduced by up to 61% compared to centrifugal fans, modulating the power consumption according to the required thermal load.
The TOP range is available in two air delivery configurations: TOPT with upflow and TOPB with downflow.
Unit supervision is developed by means of Modbus RTU protocol over RS485
serial interface as standard configuration. Other communication protocols and
interfaces are available as option.
The units are suitable for operation at a high outdoor air temperature (up to 52 C) with the correct combination with the XT remote condensers.

Versions

  • TOPT - Top air discharge and frontal intake
  • TOPB - Bottom air discharge and upper intake

Power range

  • 26,0-121 kW
  • 7,5-34,0 Ton

Factory fitted accessories

  • AP High ESP fans
  • SL Unit silencement
  • TE Electronic expansion valve
  • AT Constant air flow regulation control
  • AT/P Constant available static pressure regulation control
  • PF Differential pressure switch filters control
  • ES Electrical heater with step regulation
  • WS2 Hot water coil with 3-Way valve
  • PG Hot gas post-heating coil (with valve)
  • UMI Electrodes steam humidifier
  • SA Water alarm sensor
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB BACnet MSTP protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISS SNMP protocol, Ethernet port
  • LT Unit ready for operation with KLT
  • RE Adjustable minimum/maximum voltage and phase control relay

Loose accessories

  • MP Condensate drain pump
  • MP/U Condensate and humidifier drain pump
  • SB Fire sensor
  • SC Smoke sensor
  • CR Remote control panel
  • ZP Adjustable baseframe with shock absorbers (mod. B only)
  • ZA Adjustable baseframe with shock absorbers and deflector (mod. B only)
  • DL Bottom plenum for side connections (mod. T only)
  • BA Top vertical intake plenum with F7 efficiency filter (mod. B only)
  • BD Top frontal discharge plenum with grid (mod. T only)
  • DM Bottom frontal discharge plenum with grid (mod. B only)
  • BV Top discharge/intake plenum with damper
  • BF Direct Free-Cooling plenum for units with bottom air discharge
  • DF Direct Free-Cooling plenum for units with top air discharge